1. Overview
This module adopts standard Ovation rack plug-in mechanical structure, fully compatible with standard rack backplane slots. The stable DC power output from redundant main power supplies is fed into this distribution module and split into multiple electrically independent output branches. Each branch is equipped with replaceable fuses, voltage & current sampling circuits and status feedback loops, supplying power to designated rack slots, DPUs and I/O assemblies. Meanwhile, fault states such as fuse blowout, overvoltage, undervoltage and overload are uploaded to the DPU and upper monitoring system via the backplane bus. Every unit undergoes factory full-load durability testing, output voltage precision calibration and high-voltage insulation withstand test to guarantee long-term stable power splitting performance.
2. Core Functional Features
2.1 Multi-channel Isolated Branch Power Distribution
Realizes single-input multi-output power shunting; each output branch supplies power to a fixed group of rack modules with electrical isolation between different branches. Overload or short-circuit fault on one single branch will not propagate to other branches or the total rack input power supply.
2.2 Per-branch Independent Fuse Overcurrent Protection
Each power branch is fitted with a dedicated replaceable miniature fuse. Short circuit or overload only blows the corresponding branch fuse without causing full rack power outage; spare fuse holders are reserved for fast on-site maintenance replacement.
2.3 Real-time Sampling & Remote Upload of Power Parameters
Onboard sampling circuits continuously collect each branch’s output voltage, load current and internal module temperature. Operating data can be remotely uploaded to operator stations for real-time display and historical trend archiving.
2.4 Latched Local Fault Indication & Remote Alarm
When fuse blows, branch voltage abnormality, overload or overtemperature occurs, the module latches the fault state, activates the local front panel fault LED, and transmits an alarm signal to the upper monitoring platform for remote fault prompting.
2.5 Online Hot-swap Maintenance Support
When dual redundant main power supplies operate normally, this distribution module can be replaced online without cutting off the entire cabinet power supply; existing control logic and closed-loop regulation loops keep continuous operation with no disturbance.
2.6 Built-in EMI Filter Anti-interference Design
An input-side high-frequency filter circuit suppresses grid surges and coupled electromagnetic interference, reduces output voltage ripple, and improves the stability of working voltage for downstream control modules.
2.7 Native System Compatibility
Fully matched with Ovation standard racks, backplanes, redundant power supplies, DPUs and full-series I/O modules; no adapter boards or cabinet modifications are needed during installation, suitable for new cabinet assembly and spare part replacement during unit renovation projects.
3. Key Technical Specifications
Mounting Mode: Standard Ovation rack plug-in installation
Input Power: DC power output from rack redundant main power supply modules
Output Mode: Multiple mutually independent isolated DC power branches
Branch Protection: Independent replaceable fuse per channel, overcurrent limiting, short-circuit lockout
Monitoring Items: Branch output voltage, load current, internal temperature, fuse state
Isolation Performance: Reinforced electrical isolation between input and each output branch
Operating Temperature: 0 ℃ ~ +60 ℃
Storage & Transportation Temperature: −40 ℃ ~ +85 ℃
Relative Humidity: ≤95% RH, non-condensing
EMC Compliance: Complies with industrial G3 anti-corrosion grade and power plant cabinet anti-interference requirements
Hot-swap Restriction: Hot plugging is only permitted when dual redundant main power supplies are in normal running state
4. Front Panel LED Indicator Definition
PWR IN (Green): Steady ON = total input power normal; OFF = input power loss or abnormal
BRx OK (Green): Individual branch power normal indicator, constant illumination means normal operation
FAULT (Red): Lights up for blown branch fuse, overload, undervoltage or overtemperature; fault status latched
COMM (Green): Periodic flashing = normal data communication with backplane DPU
5. Application Scope
Thermal Power Industry
Installed in boiler, turbine, generator main control cabinets and auxiliary system cabinets, realizing partitioned power supply protection and centralized power monitoring for DPUs and all slot I/O modules in the rack.
Petrochemical Industry
Deployed in reactor, fractionator and compression unit control cabinets, implementing segmented power protection for each control loop and avoiding full-unit control shutdown caused by single branch failure.
Metallurgy, Waste Incineration Power Plants & District Heating Stations
Undertakes secondary power distribution and branch fault monitoring for automation control cabinets, ensuring long-cycle unattended stable operation of the whole production line control system.