Description
PEPPERL+FUCHS KFD2-DWB-EX1.D Rotation Speed Monitor Description
Overview
PEPPERL+FUCHS KFD2-DWB-EX1.D is a single-channel intrinsically safe rotation speed monitor belonging to the K-System isolated barrier series. This rotation speed monitor accepts NAMUR or dry contact pulse signals from hazardous area speed sensors, and the rotation speed monitor judges overspeed and underspeed status through frequency comparison. The rotation speed monitor provides relay contact outputs for safety interlock and alarm feedback, and it supports Power Rail bus connection for collective fault signaling in explosion-proof control systems.
Features
PEPPERL+FUCHS KFD2-DWB-EX1.D is designed for SIL 2 functional safety applications and carries ATEX intrinsic safety certification for hazardous locations. This rotation speed monitor supports input frequency range from 1 mHz to 5 kHz, and two independent relay contacts can be set as MIN underspeed alarm and MAX overspeed alarm separately. This rotation speed monitor has line fault detection function to identify sensor wire break and short circuit, and the built-in keypad allows on-site parameter configuration without extra programming tools. Start-up override function delays protection action up to 1000 seconds for equipment startup phase, avoiding false trip during acceleration. Galvanic isolation separates hazardous field side and safe control side, and it can be powered by terminal wiring or Power Rail feed module for flexible cabinet layout. Status LED indicators clearly display power, relay state and wiring fault for rapid diagnosis. It complies with industrial EMC standards and adapts to vibration-prone chemical, oil and gas environments.
Technical Parameters
PEPPERL+FUCHS KFD2-DWB-EX1.D belongs to K-System speed monitor family. It is a 1-channel isolated barrier, supporting NAMUR sensor or dry contact input. Input frequency range is 1 mHz to 5 kHz, with two relay contact outputs. Rated supply voltage is 20 to 30VDC, typical current consumption 100mA, power loss ≤1.8W. Safety rating is SIL 2 according to IEC/EN 61508. The housing width is 40mm, standard EN 50022 DIN rail mounting, protection grade IP20. It supports collective error message transmission via Power Rail, and the trip thresholds are adjustable through front keypad.
Working Principle
PEPPERL+FUCHS KFD2-DWB-EX1.D receives pulse signals from rotary sensors installed on monitored shafts. The rotation speed monitor converts pulse frequency into rotational speed value and compares it with preset upper and lower limit parameters. When the speed exceeds the overspeed threshold or drops below the underspeed threshold, the rotation speed monitor triggers the corresponding relay to change contact state and execute safety interlock action. If the sensor circuit suffers open circuit or short circuit, the line fault detection circuit will activate trip state to report wiring abnormality. The intrinsic safety barrier prevents energy propagation into hazardous zone, protecting the control cabinet and associated automation equipment from explosion risk.
Application Fields
PEPPERL+FUCHS KFD2-DWB-EX1.D is widely used in fans, mixers, conveyors and pump hazardous area control panels. It serves as overspeed and underspeed safety supervision unit for rotating machinery in chemical, pharmaceutical and oil & gas process safety systems. This rotation speed monitor is a common replacement spare part for maintaining Pepperl+Fuchs K-System intrinsically safe safety control systems.
Get a Quote