Reliance Electric 57401-2 16‑point 115 V AC/DC output module
Description
Product Introduction
Model Interpretation
57401‑2: Base part number; 2 = hardware revision 2
0‑57401‑2: Full AutoMax part number
57401: Family code = 115 V AC/DC output module
‑2: Revision 2 (component/layout updates, ECO fixes, drop‑in compatible with earlier revisions)
Technical Parameters
Output type: 115 VAC or 115 VDC (solid‑state, non‑isolated per channel)
Channels: 16 outputs (0–15)
Load voltage: 70–132 VAC/VDC
Load current: 0.5 A per channel, 8 A total max
On‑state resistance: <15 Ω
Off‑state leakage: <2 mA
Response time: <10 ms
Backplane power: +5 VDC, 500 mA typical
Isolation: 1500 V AC (field to backplane)
Temperature: 0 °C to +60 °C
Humidity: 5%–95% non‑condensing
Weight: ~0.91 kg (2.0 lbs)
Manual: J‑3626
Interface & Indicators
Field side: 16 screw terminals (0–15) for 115 V loads
Backplane: Edge connector for power/data
LEDs: 16 channel status; Power/Fault LEDs on front
Core Functions
Switches 115 VAC/VDC discrete loads (relays, contactors, solenoids, indicators)
Converts 5 V logic from CPU to 115 V field power
Overcurrent protection per channel (auto‑reset)
Status reporting to processor
Hot‑swap capable (system‑dependent)
Application Scenarios
Legacy AutoMax DCS/PLC output replacement in manufacturing, power, process
Factories with 115 VAC/VDC actuators and devices
Paper, steel, chemical, packaging lines
Retrofit/maintenance where full system replacement is uneconomical
57401‑2 vs 57400‑B
57400‑B: 16‑pt input (115 V AC/DC)
57401‑2: 16‑pt output (115 V AC/DC)
Both: Same form factor, backplane, rack compatibility
Operation & Maintenance
Static‑sensitive: Use ESD protection
Power off before insertion/removal/wiring
Installation: Seat firmly in rack, secure screws
Wiring: 115 V loads to terminals 0–15; common to neutral/ground
Maintenance: Keep clean/dry; inspect terminals quarterly
Troubleshooting: Check LEDs, load voltage, backplane +5 V; replace if faulty