Reliance57403‑G (0‑57403‑G)16‑point 115 VAC high‑power output module
Description
Product Introduction
Model Interpretation
57403‑G: Base model; G denotes hardware revision G (latest enhanced revision).
0‑57403‑G: Full AutoMax part number (leading 0 = standard I/O module).
57403: Product family = high‑power 115 VAC output module.
‑G: Revision with upgraded PCB, metal oxide varistor (MOV) protection, higher inrush rating, and extended temperature range; fully backward compatible with ‑D/‑E revisions.
Technical Parameters
Channels: 16 independent outputs (0–15).
Output Type: Solid‑state, 115 VAC (50/60 Hz).
Load Voltage: 70–132 VAC.
Rated Current: 2.0 A per channel; max total 32 A.
Inrush Current: 10 A peak (10 ms) for inductive loads.
Leakage Current: ≤1.5 mA (off‑state).
On‑State Resistance: <8 Ω.
Response Time: <10 ms.
Backplane Power: +5 VDC, ~650 mA.
Isolation: 2500 VAC field‑to‑logic; 1500 VAC channel‑to‑channel.
Protection: Overcurrent, short‑circuit, thermal shutdown, MOV‑based surge suppression, reverse polarity; self‑recovery after fault.
Operating Temperature: ‑10 °C to +70 °C (extended range).
Humidity: 5%–95% non‑condensing.
Weight: ~1.2 kg.
Interface and Communication Configuration
Backplane Interface: Edge connector for AutoMax dedicated backplane bus; provides power and data exchange with CPU.
Field Interface: Screw terminals (0–15) with four isolated common groups (C1–C4) (4 outputs per common).
Indicators: 16 channel status LEDs + power/fault LED on front panel.
Communication: No independent network ports; all I/O data via AutoMax backplane bus.
Core Functions
Converts 5 V logic signals from PLC into 115 VAC drive signals for high‑power field devices.
Drives motor starters, large solenoids, contactors, heaters, and high‑inrush inductive/capacitive loads.
Provides individual channel overcurrent/short‑circuit/surge protection with automatic recovery.
Feeds back channel status to CPU for diagnostics and system monitoring.
Supports hot swapping in properly configured AutoMax systems.
Application Scenarios
Replacement/maintenance of legacy AutoMax PLC/DCS in heavy industry.
Process control in metallurgy, paper, chemical, power, and oil/gas sectors.
Driving 115 VAC high‑power devices in assembly lines, material handling, and machine tools.
Systems requiring extended temperature range, high surge immunity, and high inrush current capability.
Operation and Maintenance Instructions
Installation: Power off rack before insertion; align and seat firmly, tighten mounting screws.
Wiring: Connect loads to 0–15 and commons to C1–C4; use 14–18 AWG wire, avoid over‑torque.
ESD Protection: Use anti‑static wristband/mat when handling; static may damage circuits.
Routine Maintenance: Quarterly inspection of terminals for looseness/corrosion; keep clean and dust‑free.
Troubleshooting: Check channel LEDs; verify load voltage/wiring before module replacement.
Replacement: Replace entire module if internal fault; do not repair PCB.
Get a Quote