ABB 1SBP260011R2002 (commercial model 07KR51‑R2002) compact, integrated basic controller
May 30, 2026

ABB 1SBP260011R2002 (commercial model 07KR51‑R2002) compact, integrated basic controller

ABB 1SBP260011R2002 (commercial model 07KR51‑R2002) is a compact, integrated basic controller from the Advant Controller 31 (AC31) series, optimized for small‑to‑medium industrial automation and distributed I/O applications. It integrates CPU, power supply, 8DI/6 relay DO, and communication ports into a single unit, delivering reliable logic control, data acquisition, and multi‑protocol communication in a rugged, space‑saving design.

Description

Product Introduction

ABB 1SBP260011R2002 (commercial model 07KR51‑R2002) is a compact, integrated basic controller from the Advant Controller 31 (AC31) series, optimized for small‑to‑medium industrial automation and distributed I/O applications. It integrates CPU, power supply, 8DI/6 relay DO, and communication ports into a single unit, delivering reliable logic control, data acquisition, and multi‑protocol communication in a rugged, space‑saving design.

Model Interpretation

  • 1SBP: ABB AC31/Procontic CS31 series controller prefix.

  • 260011: Base model code for 07KR51 with 120/230 V AC power.

  • R2002: Updated hardware revision (R2002, performance and reliability enhanced).

  • 07KR51: Commercial designation for AC31 basic unit with 8DI/6RelayDO.

Technical Parameters

  • Series: ABB Advant Controller 31 (AC31), Advant OCS compatible.

  • Inputs: 8 × 24 V DC digital inputs, sink/source compatible, ≤5 mA per channel, input delay 1–7 ms.

  • Outputs: 6 × relay outputs, rated 2 A @ 24 V DC / 120 V AC / 230 V AC, mechanical life ≥10⁶ operations.

  • Power Supply: 120/230 V AC ±10%, 47–63 Hz, 5 W (base) / 10 W (with expansion).

  • Processor: 400 KHz core; 64 KB battery‑buffered program/data memory.

  • Counters: 2 × hardware high‑speed counters (up to 5 kHz).

  • RTC: Integrated real‑time clock for time stamping and scheduling.

  • Operating Temperature: 0 °C to +55 °C; storage −40 °C to +70 °C.

  • Protection Class: IP20 (cabinet mounting).

  • Mounting: Standard DIN rail or screw mounting.

  • Dimensions: 127 mm × 102 mm × 127 mm; weight approx. 0.9 kg.

  • Certifications: CE, UL; manufactured in Sweden.

Interface and Communication Configuration

  • I/O Terminals: Screw terminals for 8 inputs, 6 relay outputs, and AC power terminals.

  • Programming Port: RS‑232 for programming, ASCII, or Modbus RTU communication.

  • System Bus: Integrated CS31 (RS‑485) bus, supports up to 31 remote I/O devices (total ~1000 I/O points).

  • LED Indicators: PWR, RUN, ERR, and channel‑status LEDs for diagnostics.

  • Expansion: Compatible with AC31 I/O modules (analog/digital) for system expansion.

Core Functions

  • Integrated Logic Control: Combines 8 digital inputs and 6 relay outputs for direct connection to sensors, switches, and actuators.

  • Deterministic Communication: CS31 bus enables long‑distance, high‑speed data exchange with remote I/O without reducing CPU scan performance.

  • High‑Speed Counting: Two hardware counters handle pulse counting and frequency measurement for motion/process applications.

  • Data Retention: Battery‑buffered memory preserves user program and data during power loss.

  • Diagnostics & Status: Channel‑level fault detection and LED indication for fast troubleshooting.

  • Enhanced Revision Features: R2002 revision improves EMC performance, communication stability, and thermal management.

Application Scenarios

  • Factory automation: Small production lines, assembly machines, and material handling equipment.

  • Building & HVAC: Chiller plants, air handling units, and environmental monitoring systems.

  • Water & wastewater: Pump control, valve sequencing, and level/flow monitoring.

  • Infrastructure: Lighting control, access systems, and distributed utility monitoring.

  • OEM machinery: Packaging, textile, and plastic processing equipment as a compact PLC core.

Operation and Maintenance Instructions

  • Installation: Mount vertically on DIN rail; maintain ≥50 mm clearance top/bottom for cooling; avoid vibration and direct moisture.

  • Wiring: Use AWG 14–24 copper wire; tighten terminals to 0.8 N·m; verify 120/230 V AC polarity and relay‑load voltage ratings.

  • Configuration: Program via ABB AC31GRAPH or 907AC1131 software; set I/O parameters, communication protocols, and counter functions.

  • Maintenance: Inspect terminal tightness and LED status quarterly; keep enclosure clean and free of dust/corrosive gases; replace backup battery every 3–5 years.

  • Safety: Disconnect power before servicing; do not operate with open covers or damaged wiring.


Get a Quote