Schneider 140DAI74000C Conformal Coated AC Input Module
May 16, 2026

Schneider 140DAI74000C Conformal Coated AC Input Module

140DAI74000C Modicon Quantum Discrete Input Module

Description

140DAI74000C

Modicon Quantum Discrete Input Module

16 Channels, 230 V AC, 47–63 Hz, Conformal Coated, No Fuse / No Diagnostic

English Specification Manual (Full Text, No Images)


1. General Description

140DAI74000C is a 1‑slot conformal coated AC discrete input module (non‑diagnostic, non‑fused) for Schneider Electric Modicon Quantum PLC. It provides 16 channels of 230 V AC digital input in a single group, designed for harsh, corrosive, humid, dusty, or salt‑mist industrial environments where conformal coating is required, but fuse protection and fault diagnostics are not needed.
  • Manufacturer: Schneider Electric

  • Series: Modicon Quantum (140 Series)

  • Module Type: AC Discrete Input Module, Conformal Coated, Non‑Fused, Non‑Diagnostic

  • Channels: 16 points (1 input word)

  • Form Factor: 1 slot, hot‑swappable

  • Coating: Conformal coated (IPC‑CC‑830 qualified)

  • Weight: ~0.35 kg

  • Key Feature: Conformal coated 230 V AC input, no fuse, no diagnostic LED

  • Application: Offshore, chemical, pulp & paper, high humidity, salt mist, corrosive atmosphere, general‑purpose 230 V AC signals without fuse/diagnostic requirements


2. Electrical Specifications

Same as 140DAI74000 (coating does not change electrical parameters):
  • Nominal Input Voltage: 230 V AC

  • Operating Frequency: 47 … 63 Hz

  • Logic 1 (ON):

    • 165 … 264 V AC @ 57–63 Hz

    • 175 … 264 V AC @ 47–53 Hz

  • Logic 0 (OFF): 0 … 40 V AC

  • Input Current:

    • 11.5 mA max @ 57–63 Hz

    • 9.7 mA max @ 47–53 Hz

  • Input Impedance:

    • 26.5 kΩ (capacitive) @ 57–63 Hz

    • 31.8 kΩ (capacitive) @ 47–53 Hz

  • Leakage Current: max 2.6 mA

  • Response Time:

    • OFF → ON: 0.75 … 4.9 ms

    • ON → OFF: 7.3 … 12.3 ms

  • Isolation (Channel‑to‑Bus): 1780 Vrms, 1 minute

  • Backplane Current: 180 mA

  • Power Dissipation: ~5.5 W max

  • Internal Power: Powered by Quantum backplane

  • Absolute Maximum Input:

    • 400 V AC (1 cycle)

    • 264 V AC (continuous)

    • 300 V AC (10 s)

  • Fuse: None (no replaceable fuse on module)

  • Diagnostic: None (no F‑LED, no fault indication)


3. I/O & LED Indicators (Front)

  • IN0 … IN15 (Green LEDs) – Individual input status (ON = lit)

  • ACTIVE (Green LED) – Bus communication OK

  • No F‑LED – No fuse / diagnostic indication


4. Environmental Specifications (Coating Enhanced)

  • Operating Temperature: 0 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing (coating reduces corrosion risk)

  • Altitude: ≤ 2,000 m (standard); up to 5,000 m derated

  • ESD: 4 kV contact / 8 kV air

  • EMI: 10 V/m (80–2000 MHz)

  • Protection Class: IP20

  • Coating Protection: Resists moisture, dust, salt mist, and common industrial contaminants


5. Physical & Mechanical

  • Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)

  • Mounting: Any single slot, hot‑swap compatible

  • Wiring: Screw terminals (field side)

  • Grouping: 1 group × 16 channels, 1 common

  • Field Wire Size: 0.5 … 2.5 mm²


6. Wiring & Connection

  • Common: One common for all 16 channels

  • Input: Apply 230 V AC between common and input terminal

  • Fuse: None – external fuse protection recommended

  • Shielding: Recommended for long cables; ground at one end only


7. Software Configuration

Supported software:
  • Unity Pro (recommended)

  • Concept v2.2+

  • ProWORX 32

Configuration:
  1. Add 140DAI74000C (1 slot) to I/O map

  2. Default input address: %I0 … %I15 (1 word)

  3. Set input filter (software, optional)

  4. Download to CPU


8. Troubleshooting

  • All IN LEDs OFF: Check 230 V AC supply and common wiring

  • ACTIVE OFF: Module not recognized; reseat or check backplane

  • Erratic Inputs: Poor grounding, noise, or loose terminals

  • No Fuse/DIAG: Use external circuit protection and monitoring

  • Coating Note: Do not apply additional conformal coating; factory coating is sufficient


9. Certifications

  • CE (EN 55011, EN 61131‑2)

  • UL 508 / CSA C22.2 No. 142

  • CUL, FM Class I Div 2

  • RoHS compliant

  • Coating: IPC‑CC‑830 qualified


10. Ordering Information

  • 140DAI74000: Standard non‑coated, Non‑Fuse / Non‑Diagnostic (general environment)

  • 140DAI74000C: Conformal coated, Non‑Fuse / Non‑Diagnostic (harsh environment)