Schneider 140DAI75300 AC Digital Input Module
May 16, 2026

Schneider 140DAI75300 AC Digital Input Module

140DAI75300 Modicon Quantum Discrete Input Module

Description

140DAI75300

Modicon Quantum Discrete Input Module

32 Channels, 230 V AC, 47–63 Hz, Standard Non‑Coating, 4 Isolated Groups, Diagnostic, No Fuse

English Specification Manual (Full Text, No Images)


1. General Description

140DAI75300 is a 1‑slot standard AC discrete input module (diagnostic, non‑fused) for Schneider Electric Modicon Quantum PLC. It provides 32 channels of 230 V AC digital input, arranged in 4 electrically isolated groups (8 channels per group). Designed for general‑purpose 230 V AC input applications requiring group isolation and fault diagnostics, without on‑board fuse protection.
  • Manufacturer: Schneider Electric

  • Series: Modicon Quantum (140 Series)

  • Module Type: AC Discrete Input Module, Standard, Non‑Fused, Diagnostic, 4 Isolated Groups

  • Channels: 32 points (2 input words)

  • Grouping: 4 isolated groups × 8 channels each

  • Form Factor: 1 slot, hot‑swappable

  • Coating: Standard non‑conformal coating

  • Weight: ~0.30 kg

  • Key Feature: 32×230 V AC, 4‑way isolation, diagnostic LEDs, no fuse

  • Application: Factory automation, process control, machinery, assembly lines, standard 230 V AC signals requiring group isolation and diagnostics


2. Electrical Specifications

  • Nominal Input Voltage: 230 V AC

  • Operating Frequency: 47 … 63 Hz

  • Logic 1 (ON):

    • 165 … 264 V AC @ 57–63 Hz

    • 175 … 264 V AC @ 47–53 Hz

  • Logic 0 (OFF): 0 … 40 V AC (both frequency bands)

  • Input Current (per channel):

    • ≤ 9.7 mA @ 47–53 Hz

    • ≤ 11.5 mA @ 57–63 Hz

  • Input Impedance (capacitive):

    • 31.8 kΩ @ 47–53 Hz

    • 26.5 kΩ @ 57–63 Hz

  • Leakage Current: max 2.6 mA

  • Response Time:

    • OFF → ON: 0.75 … 4.9 ms

    • ON → OFF: 7.3 … 12.3 ms

  • Isolation:

    • Channel‑to‑Bus: 1780 Vrms, 1 minute

    • Group‑to‑Group: Isolated (4 groups)

  • Backplane Current: 250 mA

  • Power Dissipation: ~5.0 W max

  • Internal Power: Powered by Quantum backplane

  • Absolute Maximum Input:

    • 400 V AC (1 cycle)

    • 264 V AC (continuous)

    • 312 V AC (10 s)

  • Fuse: None (no replaceable fuse on module)

  • Diagnostic: Yes (F‑LED + group/channel fault indication)


3. I/O & LED Indicators (Front)

  • IN0 … IN31 (Green LEDs) – Individual input status (ON = lit)

  • ACTIVE (Green LED) – Bus communication OK

  • F‑LED (Red) – Fault (overvoltage, leakage, group error)

  • Group Status LEDs – Per‑group diagnostics (8 ch/group)


4. Environmental Specifications

  • Operating Temperature: −25 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing

  • Altitude: ≤ 2,000 m (standard); up to 5,000 m derated

  • ESD: 4 kV contact / 8 kV air

  • EMI: 10 V/m (80–2000 MHz)

  • Protection Class: IP20


5. Physical & Mechanical

  • Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)

  • Mounting: Any single slot, hot‑swap compatible

  • Wiring: Screw terminals (field side)

  • Grouping: 4 isolated groups × 8 channels, 1 common per group

  • Field Wire Size: 0.5 … 2.5 mm²


6. Wiring & Connection

  • Common: 1 common per group (4 commons total)

  • Input: Apply 230 V AC between group common and input terminal

  • Fuse: None – external fuse protection recommended

  • Shielding: Recommended for long cables; ground at one end only

  • Isolation: Each group is electrically isolated from others and backplane


7. Software Configuration

Supported software:
  • Unity Pro (recommended)

  • Concept v2.2+

  • ProWORX 32

Configuration:
  1. Add 140DAI75300 (1 slot) to I/O map

  2. Default input address: %I0 … %I31 (2 words)

  3. Enable diagnostic logging (software)

  4. Set input filter (optional)

  5. Download to CPU


8. Troubleshooting

  • All IN LEDs OFF: Check 230 V AC supply and group common wiring

  • ACTIVE OFF: Module not recognized; reseat or check backplane

  • F‑LED ON: Overvoltage, leakage current, or group fault

  • Erratic Inputs: Poor grounding, noise, or loose terminals

  • Group Isolation Fault: Check inter‑group voltage and wiring


9. Certifications

  • CE (EN 55011, EN 61131‑2)

  • UL 508 / CSA C22.2 No. 142

  • CUL, FM Class I Div 2

  • RoHS compliant


10. Ordering Information

  • 140DAI75300: Standard non‑coated, Diagnostic / Non‑Fuse (general environment)

  • 140DAI75300C: Conformal coated, Diagnostic / Non‑Fuse (harsh environment)


Get a Quote