Schneider 140DAO84000C Conformal Coated AC Digital Output Module
May 16, 2026

Schneider 140DAO84000C Conformal Coated AC Digital Output Module

140DAO84000C Modicon Quantum AC Discrete Output Module

Description

140DAO84000C

Modicon Quantum AC Discrete Output Module

16 Isolated Outputs, 20–253 V AC, 47–63 Hz, Triac, Conformal Coated, Non‑Fused, No Diagnostic

English Specification Manual (Full Text, No Images)


1. General Description

140DAO84000C is a 1‑slot conformal coated AC discrete output module (triac, fully isolated, non‑fused, non‑diagnostic) for Schneider Electric Modicon Quantum PLC. It provides 16 fully isolated AC solid‑state (triac) output channels, arranged as:
  • Outputs: 16 isolated groups × 1 channel (16‑way independent isolation)

Designed for harsh / corrosive / humid / salt‑mist industrial environments requiring full channel‑to‑channel isolation, wide AC voltage tolerance, and solid‑state reliability, without on‑board diagnostics or group fuses.
  • Manufacturer: Schneider Electric

  • Series: Modicon Quantum (140 Series)

  • Module Type: AC Discrete Output Module, Triac, 16‑Ch Fully Isolated, Conformal Coated, Non‑Fused, No Diagnostic

  • Total Outputs: 16 points (fully isolated)

  • Output Grouping: 16 groups × 1 ch (each channel isolated)

  • Form Factor: 1 slot, hot‑swappable

  • Coating: Conformal coated (IPC‑CC‑830 qualified)

  • Weight: ~0.50 kg

  • Key Feature: 16×Isolated Triac Out, 20–253V AC, 47–63Hz, Full Channel Isolation, Conformal Coated, Non‑Fused, No Diagnostic

  • Application: Offshore, chemical, pulp & paper, high humidity, salt mist, corrosive atmosphere, 24/115/230V AC loads requiring isolation


2. Electrical Specifications

Outputs (16 × Isolated Triac, 20–253 V AC)

  • Output Type: Solid‑state (triac), zero‑crossing

  • Operating Voltage: 20–253 V AC

  • Nominal Voltage: 24 / 48 / 115 / 230 V AC

  • Frequency: 47–63 Hz

  • Load Current (per channel):

    • 24–115 V AC: 4 A RMS max

    • 200–230 V AC: 3 A RMS max

  • Total Module Current: 16 A RMS max (continuous)

  • Surge Current (per channel):

    • 30 A (1 cycle)

    • 20 A (2 cycles)

  • Off‑State Leakage Current:

    • 24 V AC: < 1 mA RMS

    • 115 V AC: < 2 mA RMS

    • 230 V AC: < 2.5 mA RMS

  • On‑State Voltage Drop: ≤ 1.5 V RMS

  • dv/dt Rating: 400 V/μs

  • Isolation: 2500 Vrms, 1 min (channel‑to‑channel & channel‑to‑bus)

  • Absolute Maximum Output:

    • 400 Vrms (1 cycle AC)

    • 300 Vrms (10 s AC)

Backplane & Power

  • Backplane Current: 350 mA

  • Power Dissipation: ~8.0 W max

  • Internal Power: Powered by Quantum backplane


3. I/O & LED Indicators (Front)

  • OUT0 … OUT15 (Green LEDs) – Individual output status (ON = lit)

  • ACTIVE (Green LED) – Bus communication OK

  • No FUSE LED / No Diagnostic LEDs


4. Environmental Specifications (Coating Enhanced)

  • Operating Temperature: 0 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing

  • Altitude: ≤ 2,000 m (standard); up to 5,000 m derated

  • ESD: 4 kV contact / 8 kV air

  • EMI: 10 V/m (80–2000 MHz)

  • Protection Class: IP20

  • Coating Protection: Resists moisture, dust, salt mist, and common industrial contaminants


5. Physical & Mechanical

  • Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)

  • Mounting: Any single slot, hot‑swap compatible

  • Wiring: Screw terminals (field side)

  • Output Grouping: 16 groups × 1 ch (each channel isolated, no common)

  • Field Wire Size: 0.5 … 2.5 mm² (20–14 AWG)


6. Wiring & Connection

Outputs

  • Common: No common (fully isolated channels)

  • Output: Switch 20–253 V AC between two field terminals (per channel)

  • Fuse: Non‑fused (external protection recommended)

  • Shielding: Recommended for long cables; ground at one end only

  • Polarity: AC, no polarity sensitivity


7. Software Configuration

Supported software:
  • Unity Pro (recommended)

  • Concept v2.2+

  • ProWORX 32

Configuration:
  1. Add 140DAO84000C (1 slot) to I/O map

  2. Default output address: %Q0 … %Q15 (1 word)

  3. Set output filter (optional)

  4. Download to CPU


8. Troubleshooting

  • All OUT LEDs OFF: Check backplane, module seating, or ACTIVE LED

  • ACTIVE OFF: Module not recognized; reseat or check backplane

  • OUT LED ON but load not energized: Check field wiring, load, or external fuse

  • Erratic Operation: Poor grounding, noise, or overvoltage

  • Leakage Current Issues: Use snubbers for high‑impedance loads

  • Coating Note: Do not apply additional conformal coating; factory coating is sufficient


9. Certifications

  • CE (EN 55011, EN 61131‑2)

  • UL 508 / CSA C22.2 No. 142

  • CUL, FM Class I Div 2

  • RoHS compliant

  • Coating: IPC‑CC‑830 qualified


10. Ordering Information

  • 140DAO84000: Standard non‑coated, Isolated Triac, Non‑Fused / No Diagnostic (general environment)

  • 140DAO84000C: Conformal coated, Isolated Triac, Non‑Fused / No Diagnostic (harsh environment)


Get a Quote