Schneider 140DAO85300C Conformal Coated AC Digital Output Module
May 16, 2026

Schneider 140DAO85300C Conformal Coated AC Digital Output Module

140DAO85300C Modicon Quantum AC Discrete Output Module

Description

140DAO85300C

Modicon Quantum AC Discrete Output Module

32 Outputs, 20–253 V AC, 47–63 Hz, Triac, Conformal Coated, Non‑Fused, No Diagnostic

English Specification Manual (Full Text)


1. General Description

140DAO85300C is a 1‑slot conformal coated high‑voltage AC discrete output module (triac, 4×8 grouped, non‑fused, no diagnostics) for Schneider Electric Modicon Quantum PLC. It provides 32 AC solid‑state (triac) output channels, arranged as:
  • Outputs: 4 groups × 8 channels (4×8 grouping, group‑to‑group isolation)

Designed for high‑voltage AC (115/230 V AC) in harsh/humid/corrosive environments, requiring dense I/O, group isolation, and basic ON/OFF control (no on‑board fusing or fault diagnostics).
  • Manufacturer: Schneider Electric

  • Series: Modicon Quantum (140 Series)

  • Module Type: AC Discrete Output Module, Triac, 32‑Ch (4×8), Conformal Coated, Non‑Fused, No Diagnostic

  • Total Outputs: 32 points (4 groups × 8 ch)

  • Output Grouping: 4 groups × 8 ch (group isolated, common per group)

  • Form Factor: 1 slot, hot‑swappable

  • Coating: Conformal coated (Humiseal 1A33, IPC‑CC‑830 qualified)

  • Weight: ~0.45 kg

  • Key Feature: 32×Triac Out, 20–253V AC, 47–63Hz, 4×8 Group Isolation, Conformal Coated, Non‑Fused, No Diagnostic

  • Application: 115/230V AC contactors, solenoids, lamps, small motors; offshore, chemical, pulp & paper, high humidity, salt mist, corrosive atmosphere


2. Electrical Specifications

Outputs (32 × Triac, 20–253 V AC, 4×8 Groups)

  • Output Type: Solid‑state (triac), zero‑crossing

  • Operating Voltage: 20–253 V AC

  • Nominal Voltage: 115 / 230 V AC

  • Frequency: 47–63 Hz

  • Load Current (per channel):

    • 20–253 V AC: 1 A RMS max

  • Total Module Current: 16 A RMS max (continuous)

  • Group Current: 4 A RMS max per group

  • Surge Current (per channel): ≤ 2.5 A (1 ms)

  • Off‑State Leakage Current: < 0.88 mA RMS @ 230 V AC

  • On‑State Voltage Drop: ≤ 1.5 V RMS

  • dv/dt Rating: 400 V/μs

  • Isolation: 2500 Vrms, 1 min (group‑to‑group & group‑to‑bus)

  • Absolute Maximum Output:

    • 300 Vrms (10 s AC)

    • 400 Vrms (1 cycle AC)

Backplane & Power

  • Backplane Current: 320 mA

  • Power Dissipation: ~12.0 W max

  • Internal Power: Powered by Quantum backplane

Fusing & Diagnostics

  • Fused: No (external fusing required)

  • Diagnostics: No fault LEDs or diagnostic functions


3. I/O & LED Indicators (Front)

  • OUT0 … OUT31 (Green LEDs) – Individual output status (ON = lit)

  • ACTIVE (Green LED) – Bus communication OK

  • Fault LED: None


4. Environmental Specifications (Coating Enhanced)

  • Operating Temperature: 0 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing (coating extends corrosion resistance)

  • Altitude: ≤ 2,000 m (standard); up to 5,000 m derated

  • ESD: 4 kV contact / 8 kV air

  • EMI: 10 V/m (80–2000 MHz)

  • Protection Class: IP20

  • Coating Protection: Resists moisture, dust, salt mist, and common industrial contaminants


5. Physical & Mechanical

  • Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)

  • Mounting: Any single slot, hot‑swap compatible

  • Wiring: Screw terminals (field side)

  • Output Grouping: 4 groups × 8 ch (common per group)

  • Field Wire Size: 0.5 … 2.5 mm² (20–14 AWG)

  • Weight: 0.45 kg


6. Wiring & Connection

Outputs

  • Common: Common per group (4 groups)

  • Output: Switch 20–253 V AC between common and output terminal (per channel)

  • Fuse: External fusing required (4 A max per group)

  • Shielding: Recommended for long cables; ground at one end only

  • Polarity: AC, no polarity sensitivity


7. Software Configuration

Supported software:
  • Unity Pro (recommended)

  • Concept v2.2+

  • ProWORX 32

Configuration:
  1. Add 140DAO85300C (1 slot) to I/O map

  2. Default output address: %Q0 … %Q31 (2 words)

  3. No diagnostic configuration available

  4. Download to CPU


8. Troubleshooting

  • All OUT LEDs OFF: Check backplane, module seating, or ACTIVE LED

  • ACTIVE OFF: Module not recognized; reseat or check backplane

  • OUT LED ON but load not energized: Check external fuse, field wiring, or load

  • Erratic Operation: Poor grounding, noise, or overvoltage

  • Coating Note: Do not apply additional conformal coating; factory coating is sufficient


9. Certifications

  • CE (EN 55011, EN 61131‑2)

  • UL 508 / CSA C22.2 No. 142

  • CUL, FM Class I Div 2

  • RoHS compliant

  • Coating: IPC‑CC‑830 qualified


10. Ordering Information

  • 140DAO85300: Standard non‑coated, 32×Triac 20–253V AC, 4×8 Group, Non‑Fused / No Diagnostic (general environment)

  • 140DAO85300C: Conformal coated, 32×Triac 20–253V AC, 4×8 Group, Non‑Fused / No Diagnostic (harsh environment)