Schneider Electric 490NAD91104 Profibus DP In-Line Connector
Description
Model Definition
490: Modicon network accessory series
NAD: Profibus DP connector series
91104: In‑line connector, no terminator
Technical Specifications
Hardware & Interface
Protocol: Profibus DP (RS‑485, galvanic isolation)
Connector: 9‑pin male SUB‑D, right‑angle (elbow)
Termination: None (no 120 Ω resistor)
Wiring: Screw terminals for IN/OUT bus cables
Cable entry: Side entry
Color: Violet
Dimensions: ~30 mm (H) × 55 mm (W) × 65 mm (L)
Weight: ~45 g
Pinout: Pins 3 (RxD/TxD‑N), 5 (DGND), 6 (VP), 8 (RxD/TxD‑P)
Performance & Environmental
Data rate: 9.6 kbps – 12 Mbps
Max nodes/segment: 32 (127 with repeaters)
Operating temp: 0 °C to +60 °C
Storage temp: −25 °C to +80 °C
Humidity: 5%–95%, non‑condensing
Protection: IP20
Core Functions
In‑line connection: Passes Profibus DP signal through the device for daisy‑chain wiring
No termination: Leaves bus termination to the two end nodes (use 490NAD91103 there)
Signal integrity: Matches Profibus DP electrical specs for reliable communication
Application Scenarios
Middle stations in Profibus DP networks (PLCs, drives, I/O)
Modicon M340/Momentum/Premium PLCs
ATV61/ATV71 series VFDs with DP cards
Lexium 15 motion, TeSys motor starters, Preventa Safety PLCs
Usage & Maintenance
Use only for intermediate nodes (not at bus ends)
Wire incoming bus cable to “IN,” outgoing to “OUT”
Ensure the first and last nodes use 490NAD91103 (with terminator)
Keep connections tight and dry; inspect periodically for corrosion
490NAD91103 vs 490NAD91104
490NAD91103: Ends only, 120 Ω terminator ON
490NAD91104: Middle nodes, no terminator, pass‑through